Compact 3-phase+N Type 2 surge protector - 230/400 V - Pluggable
DSM440-230/GPE
Part Number 3117200
- Compact 3-Phase Type 2 surge protector
- In : 20 kA
- Imax : 40 kA
- Common/Differential mode
- Pluggable module
- Remode Signaling contact option
- EN 61643-11, IEC 61643-11, UL1449 ed.5 compliance
The DS440 Type 2 surge protectors are compact devices designed to protect 3-phase+N networks at the main switchboard.
They provide a common or common/differential mode protection.
This SPD is based on high energy varistor equipped with thermal disconnectors and failure indicator to comply with standards.
The DS440 is DIN rail compatible and is built with a plug-in module and fixed base, which allows an easy and fast maintenance.
Select another reference:
SPD type
|
IEC | 2 |
Network
|
230/400 V 3-phase | |
AC system
|
TT-TN | |
Nominal line voltage
|
Un | 230 Vac |
Max. AC operating voltage
|
Uc | 255 Vac |
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
|
UT | 335 Vac withstand |
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
|
UT | 440 Vac disconnection |
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
|
UT | 1200 V/300A/200 ms withstand |
Residual Current
Leakage current to Ground
|
Ipe | None |
Operating current
Continious current at Uc
|
Ic | 0.5 mA |
Follow current
|
If | None |
Nominal discharge current
15 x 8/20 µs impulses
|
In | 20 kA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 40 kA |
Total Maximum discharge current
max. total withstand @ 8/20 µs
|
Imax Total | 40 kA |
Connection mode(s)
|
L/N and N/PE | |
Protection mode(s)
|
Common/Differential mode | |
Residual voltage at 5 kA
@ 5 kA (8/20µs)
|
Up-5kA | 1.5/0.9 kV |
Protection level L/N
@ In (8/20µs)
|
Up L/N | 1.25 kV |
Protection level N/PE
@ In (8/20µs)
|
Up N/PE | 1.5 kV |
Admissible short-circuit current
|
Isccr | 10 000 A |
Technology
|
MOV+GDT | |
SPD configuration
|
3-phase+Neutral | |
Connection to Network
|
By screw terminals: 1.5-10mm² (L/N) or 2.5-25mm² (PE) | |
Format
|
Plug-in modular box | |
Mounting
|
Symmetrical rail 35 mm (EN 60715) | |
Housing material
|
Thermoplastic UL94 V-0 | |
Operating temperature
|
Tu | -40/+85°C |
Protection rating
|
IP20 | |
Failsafe mode
|
Disconnection from AC network | |
Disconnection indicator
|
4 mechanical indicators | |
Remote signaling of disconnection
|
Option DS440S-230/G : output on changeover contact |
Standards compliance
|
IEC 61643-11 / EN 61643-11 / UL1449 ed.5 | |
Certification
|
Thermal disconnector
|
Internal | |
Installation ground fault breaker
|
Type 'S' or delayed | |
Back-up protection device
|
50 A min. - 125 A max. - Fuses Type gG |