Type 1+2 AC surge protector - 1-pole
DACN1-13S-10-760
Part Number 29111012
- Type 1 + 2 AC surge protector
- High energy discharge capacity(High duty)
- In: 40 kA, Imax: 80kA
- Iimp: 12.5 kA on 10/350µs impulse
- Unpluggable module for each phase
- Remote signaling
- EN 61643-11, IEC 61643-11 complied
The DACN1-13S is an high duty Type 1+2 SPD designed to protect AC powerline at the main switchboard of an installation equipped with lightning rod, and in wind turbines and photovoltaic' application.
Equipped with CITEL’s high energy discharge capacity technology, the range achieves an requirement on extreme high duty level, guaranteeing the possible application for high exposure location or/and high thunderstorm area, to ensure a more longer lifetime than expected. Furthermore, higher Uc(760Vac) and extreme low Up(3.5kV@40kA) bring advantage on wider range of application and higher protection efficiency for instructions.
Select another reference:
SPD type
|
IEC | 1+2 |
Max. AC operating voltage
|
Uc | 760 Vac |
Max. load current @25°C
|
IL | 100 A |
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
|
UT | 1000 Vac withstand |
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
|
UT | 1325 Vac disconnection |
Residual Current
Leakage current to Ground
|
Ipe | None |
Follow current
|
If | None |
Nominal discharge current
15 x 8/20 µs impulses
|
In | 40 kA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 80 kA |
Impulse current by pole
max. withstand 10/350µs by pole
|
Iimp | 12.5 kA |
Specific energy by pole
max. withstand 10/350 µs
|
W/R | 40 kJ/ohm |
Protection level
@ In (8/20µs)
|
Up | 3.5 kV |
Residual voltage at 5 kA
@ 5 kA (8/20µs)
|
Up-5kA | 2.3 kV |
Admissible short-circuit current
|
Isccr | 25 000 A |
Technology
|
MOV | |
SPD configuration
|
Single phase | |
Connection to Network
|
By screw terminals: 2.5-25mm² (35mm² rigid) | |
Format
|
1-pole modular box | |
Plugable
|
No | |
Mounting
|
Symmetrical rail 35 mm (EN 60715) | |
Housing material
|
Thermoplastic UL94 V-0 | |
Operating temperature
|
Tu | -40/+85°C |
Protection rating
|
IP20 | |
Failsafe mode
|
Disconnection from AC network | |
Disconnection indicator
|
1 mechanical indicator by pole - Red/Green | |
Remote signaling of disconnection
|
Output on changeover contact | |
Wiring for remote signaling
|
1.5 mm² max. | |
Max. Voltage/Current for remote signaling
|
250 V / 0.5 A (AC) / 30 V / 3 A (DC) | |
Dimensions
|
See diagram - 2TE (EN43880) | |
Weight
|
0.390 kg |
Standards compliance
|
EN 61643-11 / IEC 61643-11 | |
Certification
|
TUV Süd |
Thermal disconnector
|
Internal | |
Installation ground fault breaker
|
Type 'S' or delayed | |
Back-up protection device
|
Fuses Type gG - 125 A |