Type 2 AC surge protector - 3-phase+N
DAC50VGS-31-320
Part Number 821130344
- Type 2 + 3 AC surge protector
- VG Technology
- In : 20 kA
- No leakage current
- Pluggable module for each phase
- Remote signaling
- Optimized to TOV
- EN 61643-11, IEC 61643-11 and UL1449 ed.5 compliance
The pluggable surge protectors Type 2+3 DAC50VG, are designed to protect AC powerline at the main switchboard of the installation.
Equipped with the exclusive CITEL’s VG technology, the range achieves an improved protection level and a total absence of leakage current, guaranteeing a maximum protection efficiency, a simplification of use (no additional SPD required) and a maximum lifetime.
The surge protectors DAC50VG, are available in multipolar version and in several voltages to protect single or 3-phase networks.
Select another reference:
SPD type
|
IEC | 2+3 |
Network
|
230/400 V 3-phase+N | |
AC system
|
TT-TNS | |
Max. AC operating voltage
|
Uc | 320 Vac |
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
|
UT | 335 Vac withstand |
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
|
UT | 440 Vac withstand |
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
|
UT | 1200 V/300A/200 ms withstand |
Residual Current
Leakage current to Ground
|
Ipe | None |
Follow current
|
If | None |
Nominal discharge current
15 x 8/20 µs impulses
|
In | 20 kA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 50 kA |
Total Maximum discharge current
max. total withstand @ 8/20 µs
|
Imax Total | 50 kA |
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
|
Uoc | 6 kV |
Connection mode(s)
|
L/N and N/PE | |
Protection level
@ In (8/20µs) and @ 6 kV (1,2/50 µs)
|
Up L/N | 1.5 kV |
Protection level N/PE
@ In (8/20µs) and @ 6 kV (1,2/50 µs)
|
Up N/PE | 1.5 kV |
Residual voltage L/N at 5 kA
@ 5 kA (8/20µs)
|
Up-5kA | 0.9 kV |
Protection level N/PE at 5 kA
@ 5 kA (8/20µs)
|
Up-5kA | 0.9 kV |
Admissible short-circuit current
|
Isccr | 50 000 A |
Network type
|
AC | |
Technology
|
VG Technology (MOV+GSG) | |
SPD configuration
|
3-phase+Neutral | |
Connection to Network
|
By screw terminals: 2.5-25mm² (35mm² rigid) | |
Format
|
Plug-in modular box | |
Plugable
|
Yes | |
Mounting
|
Symmetrical rail 35 mm (EN 60715) | |
Housing material
|
Thermoplastic UL94 V-0 | |
Operating temperature
|
Tu | -40/+85°C |
Protection rating
|
IP20 | |
Failsafe mode
|
Disconnection from AC network | |
Disconnection indicator
|
1 mechanical indicator by pole - Red/Green | |
Spare module(s)
|
MDAC50VG-320 + MDAC50G-255 | |
Remote signaling of disconnection
|
Output on changeover contact | |
Wiring for remote signaling
|
1.5 mm² max. | |
Max. Voltage/Current for remote signaling
|
250 V / 0.5 A (AC) / 30 V / 3 A (DC) | |
Dimensions
|
See diagram - 4TE (EN43880) | |
Weight
|
0.355 kg |
Standards compliance
|
IEC 61643-11 / EN 61643-11 / UL1449 ed.5 | |
Certification
|
KEMA |
Thermal disconnector
|
Internal | |
Installation ground fault breaker
|
Type 'S' or delayed | |
Back-up protection device
|
50 A min. - 160 A max. - Fuses Type gG |