Combined AC/Dataline surge protector for LED lighting system Class 1
MLPCH1-230L-V/DL
Part Number 833223
- Type 2 (or 3) surge protector for Class 1 LED Lighting
- Combined AC/Dataline surge protection
- DALI, DMX, RS485, 0-10V datalines compliance
- Shield wire management
- Optimized coordination with driver
- Compact dimensions
- Screw connection
- Max. discharge current 10 kA
- Certified IEC 61643-11 and IEC 61643-21
The MLPCHx-V/DL surge protectors have been designed to protect single-phase DALI-powered equipment. Designed for optimum coordination with the driver, the range offers an excellent performance ratio.
The products can be used as Type 2 + 3, thanks to their very compact design and their maximum discharge capacity of 10 kA per pole. Connection is via opposing screw terminals (MLPCHx-230L-V).
The products comply with IEC 61643-11 and IEC 61643-21.
Select another reference:
Isolation classe
|
I | |
Network
|
230 V single-phase | |
AC system
|
TT-TN | |
Max. Data operating voltage
|
Uc | 28 Vdc |
Max. AC operating voltage
|
Uc | 320 Vac |
Max. load current @25°C
|
IL | 2.5 A |
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
|
UT | 335 Vac withstand |
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
|
UT | 440 Vac disconnection |
Residual Current
Leakage current to Ground
|
Ipe | None |
Nominal discharge current
15 x 8/20 µs impulses
|
In | 5 kA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 10 kA |
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
|
Uoc | 10 kV / 5 kA |
Protection mode(s)
|
Common/Differential mode | |
Protection level
@ In (8/20 µs)
|
Up L/L | 50 V |
Protection level L/N
@ In (8/20µs)
|
Up L/N | 1.5 kV |
Protection level N/PE
@ In (8/20µs)
|
Up N/PE | 1.5 kV |
Line/Line Nominal discharge current
C2 Category
|
In L/L | 5 kA |
Admissible short-circuit current
|
Isccr | 10 000 A |
Technology
|
MOV+GDT | |
Connection to Network
|
By screw terminal: 1.5mm² max. | |
Mounting
|
On plate | |
Housing material
|
Thermoplastic UL94 V-0 | |
Operating temperature
|
Tu | -40/+85°C |
Protection rating
|
IP20 | |
Failsafe mode
|
Disconnection, Green Led OFF and power cut off | |
Disconnection indicator
|
LED green OFF and AC network cut-off | |
Dimensions
|
See diagram | |
Weight
|
0.056 kg |
Standards compliance
|
IEC 61643-11 / EN 61643-11 / IEC 61643-21 / EN 61643-21 / UL1449 ed.5 | |
Certification
|