1-pair DIN rail plug-in Data surge protector
DLAWTS1-48D3
Part Number 6421041
- Surge protection for 1-pair
- Pluggable protection module
- Optical fault indication
- Remote signalling (DLAWTS1-48DC required for power supply)
- Indirect shield connection
- Indirect earthing
- Signal interruption when module is disconnected
- Conforms to IEC 61643-21, VDE 0845-3-1 and UL497B
The surge protection devices of the DLAWTS series protect I&C, telecommunication and data technology systems against lightning effects and overvoltages. These surge protectors have been developed for the protection of one twin wire and can be used for all applications with voltages from 6 V to max. 170 V and transmission rates up to 10 Mbps. The electrical circuitry of the DLAS consists of a combination of high-performance gas discharge tubes and fast-switching diodes for high discharge capacity and fast response. The shield connection is additionally earthed via a gas discharge tube. Earthing is simply done via the top-hat rail. When the plug-in module is disconnected, the transmission signal is interrupted. Error signalling is via a visual display and remote signalling.
Select another reference:
Network
|
RNIS-T0, 48 V line | |
Nominal line voltage
|
Un | 48 V |
Max. AC operating voltage
|
Uc | 37 Vac |
Max. DC operating voltage
|
Uc | 53 Vdc |
Max. frequency
|
f max. | > 3 MHz |
Insertion loss
|
< 1 dB | |
Max. load current @25°C
|
IL | 300 mA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 20 kA |
Line inductance (± 10 %)
|
non | |
Protection mode(s)
|
Common/Differential mode | |
Protection Level
C3 (10/1000μs), 300 applications@10 A, X-X (Line/Line)
|
Up | 70 V |
Protection level
C3 (10/1000μs), 300 applications@10 A, X-C (Line/Earth)
|
Up | 70 V |
Max. capacitance
|
C | < 50 pF |
Impulse current
2 x 10/350µs Test - D1 Category
|
Iimp | 5 kA |
Nominal discharge current
C2 Category
|
In | 5 kA |
Line/Line Nominal discharge current
C2 Category
|
In L/L | 5 kA |
Nominal Discharge Current, X-C (Line/Earth)
8/20µs Test x 10 - C2 Category
|
In L/PE | 5 kA |
Line resistance (± 10%)
|
4.7 Ohm |
Network type
|
Data Communication | |
Technology
|
GDT+Clamping diode+PTC (thermal resistor) + Resistor | |
SPD configuration
|
1-pair+shielded | |
Connection to Network
|
By screw terminal: cross section 0.5-2.5mm² | |
Format
|
Plug-in DIN box | |
Mounting
|
Symmetrical rail 35 mm (EN 60715) | |
Housing material
|
Thermoplastic UL94 V-0 | |
Operating temperature
|
Tu | -40/+85°C |
Protection rating
|
IP20 | |
Failsafe mode
|
Specific version with line cut-off in case of removal plug-in module | |
With line cut-off in case of removal plug-in module
|
Yes | |
Disconnection indicator
|
Red light on | |
Spare module(s)
|
DLAWTS1M-48D3 | |
Remote signaling of disconnection
|
Trough control module | |
Connection bus
|
SPD connection/control module by bus: bus 1+4 (1control module+4 SPD), bus 1+9, bus 1+24 and bus 1+48 | |
Dimensions
|
See diagram |
Standards compliance
|
IEC 61643-21 / EN 61643-21 / UL497B |