1-pair monobloc Telecom surge protector
DLC-24D2
Part Number 641183
- High speed data transmission
- Common mode and differential mode protection
- Data lines, including those isolated from Earth
- Compact DIN rail enclosure, high density protection
- Protection of shield wire
- Location and test categories: D1, C2, C3
- IEC 61643-21 compliance
DLC compact surge protective devices (SPDs) are designed to protect terminal equipment connected to industrial buses, telecommunication lines or signalling applications from the effects of lightning and transient overvoltages. These SPDs are installed on symmetrical DIN rail, often within customer panels. DLC SPDs protect 1-pair applications and have a non-pluggable (monobloc) enclosure.
Many types are available to cover most applications. D2 types are best suited to floating applications, D3 types offer full-mode protection across all lines with D3G types additionally providing specific protection for the signalling ground wire.
Select another reference:
Network
|
4-20 mA, 24 V analogic | |
Nominal line voltage
|
Un | 24 V |
Max. DC operating voltage
|
Uc | 32 Vdc |
Max. frequency
|
f max. | > 50 MHz |
Insertion loss
|
< 1 dB | |
Max. load current @25°C
|
IL | 750 mA |
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 20 kA |
Line inductance (± 10 %)
|
non | |
Protection Level
C3 (10/1000μs), 300 applications@10 A, X-X (Line/Line)
|
Up | 60 V |
Protection level
C3 (10/1000μs), 300 applications@10 A, X-C (Line/Earth)
|
Up | 650 V |
Impulse current
2 x 10/350µs Test - D1 Category
|
Iimp | 2.0 kA |
Line/Line Nominal discharge current
C2 Category
|
In L/L | 10 kA |
Nominal Discharge Current, X-C (Line/Earth)
8/20µs Test x 10 - C2 Category
|
In L/PE | 10 kA |
Line resistance (± 10%)
|
1.2 Ohm |
Network type
|
Data Communication | |
Technology
|
GDT+TVS diode | |
SPD configuration
|
1-pair+shielded | |
Connection to Network
|
By spring terminal - max. cross section 2.5mm² / AWG 13 (solid or stranded) | |
Compact
|
Yes | |
Format
|
DIN box | |
Mounting
|
Symmetrical rail 35 mm (EN 60715) | |
Housing material
|
Thermoplastic UL94 V-0 | |
Operating temperature
|
Tu | -40/+85°C |
Ingress Protection rating
|
IP20 (NEMA 2) | |
Failsafe mode
|
Short-circuit | |
Disconnection indicator
|
Transmission interrupt - default mode 2 | |
Dimensions
|
See diagram | |
Weight
|
0.029 kg |
Standards compliance
|
IEC 61643-21 / EN 61643-21 | |
Certification
|
SIL |